Rack Layout in USC55 (version 7.5)

Both floors are shown. Racks are installed out to #11, 15 on S1,2. Row A is closest to the shaft. Racks 0 (S1) and 1 (S2) are closest to the interaction hall (UXC55).  Rack rows are spaced 1.5 m front face to front face (B-C,D-E,F-G,H-J)) and 1.0 m rear face to rear face (A-B,C-D,E-F,G-H,J-K). *There is a 30 cm underfloor structural beam between racks 8 & 9 (and 17 & 18 on S1). #There is a 30 cm gap between racks S1C08 and S1C09 and also between S1F08 and S1F09 for a vertical structural column. %There are holes between the floors located at E03, E05 and F05. RED RACKS HAVE CRITICAL LENGTH FIBERS TO THE DETECTOR. GREEN RACKS HAVE NON-CRITICAL PATH FIBERS TO THE DETECTOR. DAQ RACKS ARE BLUE. GREY RACKS ARE RESERVATIONS. Definition of abbreviations. Information about racks. Rack Wizard (rack entry tool). Descriptions of S1 Racks. Descriptions of S2 Racks. PC entry tool.
Green Shaded Racks have automatic fire suppression. Yellow-shaded racks are standard PC racks

+Z      Upper Floor (Zone S2)      -Z  
  A B C D E F G H
01 -- -- -- ECAL spare Cal Reg Trig HCAL HTR -- --
02 TOTEM TOTEM DAQ ECAL ULR Cal Reg Trig HCAL HTR DAQ x
03 TOTEM TOTEM CASTOR HV ECAL ULR %Cal Reg Trig HCAL HTR EBE DCS x
04 TOTEM TOTEM CASTOR HV ECAL ULR Cal Reg Trig HCAL HTR EBE DCS x
05 TOTEM DAQ UX DCS ECAL SRP/TST %Cal Reg Trig %HCAL HTR Presh. HV x
06 RAMSES EB HV HCAL DCS ECAL ULR Cal Reg Trig HCAL HTR EB HV x
07 Access EB HV HCAL DCS ECAL ULR Cal Reg Trig HCAL HTR EB HV x
*08 ASSM

EB HV

HCAL SrcDrv

ECAL ULR Cal Reg Trig HCAL HTR

EB HV

x
*09 ASSM EE HV
HPD HV

DAQ

Cal Reg Trig HCAL HTR EE HV x
10 ASSM Presh. DCS
HPD HV
FRL PC Cal Reg Trig DAQ Presh. DCS x
11

ASSM

ECAL LV
HPD HV
x TOTEM Trig EBE Lt Mn ECAL Cool DSS
12

ASSM

ECAL LV
HPD HV
x
CASTOR Trig
EBE Lt Mn ECAL Cool DSS
13 ASSM
Presh. LV
HPD HV
Presh. Misc ZDC EBE Lt Mn ECAL Cool DSS
14

ASSM

Rack Pwr
PMT HV
Presh. Misc
DAQ PP
EB Misc EE Misc DSS
15 ASSM Rack Pwr
DSS
DSS
DSS
DSS
DSS DSS

  <-- Passageway -->

16 Fire Det. TTC PCs DAQ PC DAQ Switch Netwk DCS PCs Spare PCs UPS PCs
*17 Fire Det. TK PCs DAQ PC DAQ Switch Netwk HCAL PCs Trig PCs
UPS PCs
*18 Fire Det. TK/Pixel PCs DAQ PC DAQ Switch Netwk ECAL DCS/ES PCs Muon PCs
UPS PCs
19 Fire Det. TOTEM PCs DAQ PC DAQ Switch Netwk ECAL FED PCs Align PCs
UPS PCs

+Z     Lower Floor

 (Zone S1)

   

-Z 

  A B C D E F G H
00
--
-- Presh. ULR Presh. ULR
TK. FEC
TK. FEC DT/RO/SC --
01
--
-- DAQ DT TrkFnd

Opt.Cpl.

RPC Trig Pixel FEC --
02

TK. Ctrl

DAQ DAQ DT TrkFnd TTC RPC Trig
Pixel Ctrl
RPC B HV
03

TK. Ctrl

TK. FED TIB+TID TK. FED TOB DT TrkFnd %TTC RPC Trig

Pixel FED

RPC B HV
04

TK. Ctrl

TK. FED TIB+TID

TK. FED TOB

CSC TrkFnd

Global

RPC Trig Pixel FED RPC B HV
05

TK. Ctrl

TK. FED TIB+TID

TK. FED TOB CSC TrkFnd %Cal Global %RPC Trig

DAQ

RPC B HV
06

TK. Ctrl

DAQ DAQ FRL PC TTS
DAQ

CSC FED

RPC B HV
07

TK. Ctrl

DAQ DAQ DT HV

TTS

x CSC FED RPC B HV
*08

TK. Ctrl

TK. FED TEC-

TK. FED TEC+# DT HV BPTX BRM# CSC FED

RPC E+ HV

*09

TK. Ctrl

TK. FED TEC- TK. FED TEC+# DT HV LHC DAQ# DAQ PP

RPC E+ HV

10 TK LV Mon TK. FED TEC- TK. FED TEC+ DT HV

BPM

DSS ME1/1 HV

RPC E- HV

11 CSC HV DAQ DAQ DT HV DSS DSS DSS RPC E- HV
12 CSC HV

TK. Ctrl

Work Area
DAQ PC
Work Area
Work Area Work Area Work Area
13 CSC HV

TK. Ctrl

Work Area
Work Area
Work Area
Work Area Work Area Work Area
14 BCAM

TK. Ctrl

Work Area
Work Area
Work Area
Work Area Work Area Work Area
15 Rack Pwr

TK. Ctrl

Work Area
Work Area
Work Area
Work Area Work Area Work Area

 <-- Passageway -->


Version History:
(previous versions available as: http://cmsdoc.cern.ch/~wsmith/USC55_racks_vxy.html, where x.y is version below)
2.1:  26.05.99: Starting Point
2.2:  01.09.99: Added ME1/1 HV in H11, H12
2.3:  06.09.99: Removed 15th rack from each row in the lower floor
2.4:  04.09.99: Changed Row I to J and labelled all rows with 2 digits
2.5:  01.06.00: ECAL Revisions
2.6:  19.07.00: Preshower FEC, Laser & LV/HV additions, Track. PS from 11 to 20.
2.7:  07.02.01: Add new rack row K and 8 ASSM Racks, redistribute EE LV & EB LV
2.8:  30.05.01: Remove DCS, add Ctrl/Safety, redistribute Track. PS, CSC HV, ME1/1 HV, Presh. HV/LV (+add 1), add 2 CSC FED, add 5 RPC HV
2.9: 25.10.01: Move Presh. LV/HV/Misc to Upper Floor, redistribute EBE HV/LV,add DAQ Racks,reduce/move CSC & DT Trackfinder Racks
3.0: 01.11.01: Remove lower floor passageway. Move upper floor passageway to between racks 14 and 15 in each row. Correct # EE LV, EB HV.
3.1: 10.12.01: Exch. RPC B/EC for 8 RPC Trig., add Opt. Cpl,TTC/FM, and reserve, move Track/Presh. FEC, CSC & DT TrkFnd, ME1/1 HV
3.2: 07.02.02: Add Pixel racks: 2PS, FED,FEC,Ctrl.Move CSC FED &HV, DT HV, RPC EC HV,DAQ,Track.PS
3.3: 20.06.02: Add color codes for racks with fibers to the detector. Add one CSC FED Rack.
3.4: 24.09.02: Add color codes for power supply racks to be removed. Changed Zone Labels.
3.5 01.10.02: Removed LV Power Supplies, ECAL racks. Redistribute EE/EB HV, CSC HV, HPD HV
3.6 12.11.02: Moved Presh FED, Rearranged Tracker FEDs lower floor rows B, C. Added DAQ rack for TOTEM.
3.7 29.11.02: Swap columns S2: A, B, C, D, with F, G, H, J (HCAL to RPC thru floor), remove one RPC HV rack, remove column S2/K, mark holes, add alignment racks, remove DT FED & SC and put in DT TR/RO/SC.
3.8 04.12.02: Remove column S2/J and redistribute column J racks, add DAQ rack to S2/C1, TTC/FM->TTC, S2 E6,7 -> TTS and move DAQ Rack E7->E8.
3.9 30.01.03: Add HCAL Source Driver Rack & 09.04.03: S1G01: 'DT TR/RO/SC'-> 'DT RO/SC'.
4.0: 08.05.03: Remove ECAL S2 C18,F9-10, G4-7,move ASSM, remove LESS, add F.D., TKPS res, rename control/safety DSS, remove HEALTH, remove CSC HV racks S1 G10-14, remove 2 HCAL Calib, add 1 Pixel FED, add EE & EB LV, increase RPC HV to 6B+4E, swap RPC & DT HV rows, 1 presh misc -> DCS, 1 HCAL HPD -> PMT.
4.1: 24.06.03: Add BPTX Rack for LHC machine monitors, move Presh DCS/HV/LV to make room.
4.2: 10.07.03: Move BPTX ->S1E08 , add adjacent LHC Rack, swap RPC B HV <-> DT HV, move DAQ to make room.
4.3: 24.07.03: Move 1 RPC B HV S1F->S1E & move rest of RPC HV back 1 rack, move DAQ S1E10 -> S1F07.
4.4: 30.10.03: Move EB HV (C,D,G15-16) to (B5-7,G5-7), EE HV (C17,G17) to (B8,G8), Presh. HV/LV (B15-17,H9-11) to (B9-11,G9-11) EB LV, EE HV (C18, G18) to (G12,G13) Presh. DCS (H8) to (G4)
4.5: 31.10.03: S2: Move TOTEM (A1-3) to (B1-3), HPD & PMT HV (E,F15-17) to (C8-13), F.D. (H14-16) to (H9-11), DSS (A,B,D,F,H18) to (C,D,F,G,H14)
4.6: 03.11.03: Add BPM (S1E12). Move Align PCs, Laser S2(B12,13) to (H5,6), DSS S2(C14->B14), Presh Misc. S2(B14->12)
4.7: 25.02.04: Swap rows D and F on both floors and C and G on S2, move hole between floors at D05 to F05, move EBE Lt.Mon.,Laser (H1-4) to (D10-13), move align PCs and Align Laser (H6,7) to (E13,14).
4.8: 28.02.04: Swap back C2-13 and G2-13. Add DAQ rack to S1 F11.
4.9: 05.03.04: Move the EBE Lt. Mon. & Laser Racks in S2 D10-13 to S2 F10-13, move Presh FED in S1 B12,13 to S2 D10,11, add DAQ rack in D12
5.0: 15.03.04: Remove one TOTEM rack at S2 A4. Add a TOTEM trigger rack in S2 E11.
5.1: 18.03.04: Add one TOTEM rack at S2 A4. Move Pixel Ctrl (S1H1->B13), Trk Ctrl (S1C14->B12), DSS (H14->C14).
5.2: 29.03.04: Reorganize ECAL ULR racks, Add one CASTOR trigger rack at S2E12, move 1 DT HV rack (S1G14->S1F14), move 1 DSS rack (S1F14->S1A14), shift CSC HV racks by 1 closer to UX (S1A10-14->S1A9-13), shift Pixel FED, DAQ, CSC FED, DT HV by 1 farther from UX (S1G3-13->S1G4-14), move Pixel Ctrl (S1B13->S1G3).
5.3: 01.05.04: Reorganize ECAL ULR racks: shift+1, spare: S2D8->1, add IT Division Network racks in S2 A16-18.
5.4: 04.05.04: Shift S1DEFG+2, S2DEF+1, change Rack numbering +1, include row 00 in S1. Swap RPC HV E<->B: S1E12-15<->D12-15, Swap ME1/1 HV <-> DT HV: S1F13-14 <-> S1G13-14. Move TK Ctrl S1B13->S1C15. Move DSS S1C15->S1G15, Remove one CSC FED rack containing CPU farm, Add two ECAL Cooling control racks.
5.5: 05.05.04: Move Tracker PS racks. Redistribute other PS racks. Move DAQ rack: B12->A11. Add one Rack Power Control rack to each floor.
5.6: 12.05.04: Shift S1C+2. Move DAQ Rack S1A11->S1C01. Remove Presh FED & DAQ Racks S2D10-12 & FEC Rack S1D00. Add 2 Presh. ULR racks in S1D00,C00. Remove DAQ Rack S1C08. Move TK FED Racks S1C09-11 to S1C08-10. Add TK PS Res at S1A12. Move FED PC rack: S1B07->S2E16. Move DAQ Rack: S1C08->C11. Move TK FED TEC+/- racks: S1B,C: 9-11 -> 8-10. Add DAQ Rack: S1B11. Change S2G05: Presh. DCS -> Presh. HV. Change S2B,G10: Presh. LV/HV -> Presh. DCS. Change S2B11-13,G11-12: Presh. LV/HV -> Presh. Misc. Change S2G13,14: EB,EE LV -> EB,EE Misc.
5.7: 02.06.04: ECAL Cool <-> Presh. Misc. (S2D13-14 <-> S2G11-12), S2G13: EB. Misc -> ECAL Cool.
5.8: 08.06.04: Align Laser (S2E15) moved to Laser Room. EBE Laser (S2F14) -> misc. Align PCs (S2E14) ->S2F19.
5.9: 15.07.04: B11,12,13 (Presh Misc -> ECAL LV, Presh LV) name change, TK PS Res (S1A-E:12-15) removed.
6.0: 30.08.04: Move CSC HV racks (S1A06-10->S1A10-14). Add 4 TK Ctrl. racks (S1A06-9). Move DAQ rack (S2F09->10). Add HCAL HTR rack (S2F09). Add 2 fire detection racks (S2A16,17). Add 2 RAMSES racks (S2A18,19). Move DSS rack (S2B14->S2E15). Add Rack Pwr rack (S2B14).
6.1: 12.10.04: Remove 2 ASSM racks (S2A6,7). Move 2 RAMSES racks (S2A18,19 -> S2A6,7). Add 2 Fire Det. racks (S2A18,19). Add 4 DAQ Switch Racks (S2D16-19).
6.2: 10.12.04: Specify racks with fire suppression. Convert DAQ rack S1D6 to DAQ PC rack. Add DAQ PC rack S2D10.Identify S1B-H(12-15) as a work area without racks. Identify Racks S2B-G(16-19), S1D06, and S2D10 as PC-style racks with horizontal airflow.
6.3: 24.03.05: Add fire protection to DAQ FRL racks: S1B2, S1B6, S1B7, S1B11, S1C1, S1C2, S1C6, S1C7, S1C11, S1F9, S1G5,S2B5, S2C2, S2D9, S2F10, S2G2.
6.4: 11.04.05: Change S2C16-19 PC racks to DAQ RU/BU/FU PC racks. Change S2D10 and S1D6 from DAQ PC racks to FRL PC racks.
6.5: 24.06.05: Remove RPC Trigger racks S1F06-8.Remove ME1/1 HV rack S1G10. Add DAQ Rack S1F06, S2A07: RAMSES->Access Control.
6.6: 29.08.05: Remove HCAL Calib racks S2C03-4. Add UX DCS rack S2C05. Move FED PC Rack (S2E16->S2B19). Add Network rack (S2E16).
6.7: 28.11.05: Move ME1/1 HV rack(S1G09->10). Add DAQ Fiber Patch Panel Racks in S1G09 and S2E14. Add hole between floors at E03 for TTC fibers.
6.8: 07.02.06: Install 4 new DSS racks in S2H12/13/14/15.
6.9: 02.03.06: Add ZDC rack in S2E13, specify assignment of PCs.
7.0: 16.03.06: Add Alignment PC Rack in S2G19.
7.1: 21.03.06: Add 2 CASTOR HV racks in S2C3,4.
7.2: 31.03.06: Add DCS PC rack in S2F17. Add 4 TK CTRL racks in S1B12-15..
7.3: 18.04.06: Rearrange PC racks.
7.4: 09.10.06: Add BRM rack in S1F08. Add DAQ PC rack in S1D12. Add UPS PC racks in S2H16-19. Add DSS rack in S2H11.
7.5: 23.11.07: Switch: S1A10: CSC HV -> TK LV Mon, S1A14: CSC HV -> BCAM.
 

Last Updated on 23.11.07